The
role of the Lightning Protection system is to provide a preferred
point of attachment to a lightning stroke, and then safely conduct
its associated lightning current to ground safely, and in such a
controlled manner so as to minimize the issues of magnetic induction
on to parallel run cabling and conductors, whilst minimizing the
likelihood of side-flash.
In
providing this basic function, it is necessary to consider such
important aspects as human safety, as any local interaction and
trafficking by humans in conducting their ordinary duties whilst
in close proximity to these LP and Earthing systems, has a risk,
whilst the segregation of internal cabling systems and sensitive
equipment from the elevated electro magnetic fields generated
by down-conductors and earthing systems during lightning strikes,
is also an important consideration.
It
is important to ensure that any lightning Protection system down-conductor
is connected to a low R (resistance) and low Z (characteristic
impedance) earthing system, one which is designed to dissipate
the lightning current into the ground as quickly as possible,
whilst minimizing ground potential rise, and maximizing the potential
fall-off, away from the currents earth injection point.
The
Australian Standard AS/NZS 1768-2007 “Lightning Protection” provides
useful guidance in this respect, and it is recommended that whilst
this is not a “mandatory” standard, if the recommendations and
design considerations are implemented in their entirety, the greatest
level of acceptable protection can be afforded to both equipment
and personnel.
The
generic Lightning Protection design methodology that is endorsed
in the AS1768 Standard is based on the adoption of the Rolling
Sphere Methodology (RSM), which is used in determining zones of
protection. In this methodology, an imaginary sphere of specified
radius (based on design protection levels “see below”) is theoretically
brought up to, and rolled over the total structure to be protected.
All sections of the structure that the sphere touches are considered
to be exposed to direct lightning strokes, and would need to be
protected by the placement of air terminals (lightning rods).
The illustration below visually demonstrates the
concept behind Rolling Sphere Method (RSM). Note that the 45 mtr
sphere sits atop the air rods, thereby providing an air gap between
the sphere and the structure.

In
general, air terminals need to be installed in such a manner
so that the rolling sphere only touches their upper interception
surfaces, and when/ if the sphere touches or breaches the outer
fabric of the structure, then additional air terminals should
be installed at those points. The values of the rolling sphere
radius are based on four protection levels:
Protection
Level 1 |
20
Mtr Rolling Sphere |
Protection Level
2 |
30 Mtr Rolling
Sphere |
Protection
Level 3 |
45 Mtr Rolling
Sphere |
Protection Level
4 |
60 Mtr Rolling
Sphere |
AS1768-2007
provides the relevant radius of the rolling sphere for each protection
level, together with the corresponding minimum lightning current
(Imin) that will be intercepted.
Rolling
Sphere Radius for Each Protection Level
Protection
Level |
Sphere
Radius |
Interception
Current
I min-kA
|
I |
20 |
2.9 |
|
II |
30 |
5.4 |
III |
45 |
10.1 |
IV |
60 |
15.7 |
For
normal applications Protection Level 3 is recommended using the
45 Mtr rolling sphere. Where munitions, fireworks or explosives
are concerned Protection Level 1 is required using a 20 mtr rolling
sphere.
Conventional
Design using 45Mtr RSM

Conventional Lightning Protection Systems
should be designed and installed during a structures construction
as this type of Lightning Protection system can be difficult to
retrofit to existing buildings, and would require down conductors
to be installed vertically on the external walls every 20 mtrs.
These conductors also require to be clipped every meter or so,
hence the LP system be visually unsightly and can detract from
the aesthetics of the building markedly.
During construction, structural rebar within
the concrete may be used to carry lightning current to ground
where there is a continuity of the rebar from roof to ground.
Where this continuity is not assured, the use of dedicated down
conductors is recommended.
These systems are very labor and component
intensive, where the install costs can be considerable as an overall
percentage of the systems cost.
Alternatively
there is another Lightning Protection system which is commonly
used, although is outside of the scope of the AS1768 Lightning
Protection standard, the Non Conventional “System 3000” Lightning
Protection System.
Non-Conventional
Systems 3000 LPS
The System 3000 is
not covered in and is outside the scope of the current AS/NZS
1768-2007 Lightning Protection standard, but are proven to be
effective and are simple and easy to retrofit to existing buildings.
The system generally require very few down conductors, (the down
conductor is a special design coaxial cable) which are relatively
flexible and can be route current away from any sensitive areas.
The condustor can be taken down areas of the structure which do
not distract from the aesthetics. A single LPS would require a
single coaxial down-conductor.
As
installation would generally take a day or so, compared to a conventional
type system, significant cost savings can be realized by the use
of System 3000