|
The role of the Lightning Protection system is to provide
a preferred point of attachment to a lightning stroke, and
then safely conduct its associated lightning current to
ground safely, and in such a controlled manner so as to
minimize the issues of magnetic induction on to parallel
run cabling and conductors, whilst minimizing the likelihood
of side-flash.
In providing this basic function, it is necessary to consider
such important aspects as human safety, as any local interaction
and trafficking by humans in conducting their ordinary duties
whilst in close proximity to these LP and Earthing systems,
has a risk, whilst the segregation of internal cabling systems
and sensitive equipment from the elevated electro magnetic
fields generated by down-conductors and earthing systems
during lightning strikes, is also an important consideration.
It is important to ensure that any lightning Protection
system down-conductor is connected to a low R (resistance)
and low Z (characteristic impedance) earthing system, one
which is designed to dissipate the lightning current into
the ground as quickly as possible, whilst minimizing ground
potential rise, and maximizing the potential fall-off, away
from the currents earth injection point.
The Australian Standard AS/NZS 1768-2007 “Lightning Protection”
provides useful guidance in this respect, and it is recommended
that whilst this is not a “mandatory” standard, if the recommendations
and design considerations are implemented in their entirety,
the greatest level of acceptable protection can be afforded
to both equipment and personnel.
The generic Lightning Protection design methodology that
is endorsed in the AS1768 Standard is based on the adoption
of the Rolling Sphere Methodology (RSM), which is used in
determining zones of protection. In this methodology, an
imaginary sphere of specified radius (based on design protection
levels “see below”) is theoretically brought up to, and
rolled over the total structure to be protected. All sections
of the structure that the sphere touches are considered
to be exposed to direct lightning strokes, and would need
to be protected by the placement of air terminals (lightning
rods).
The illustration below visually demonstrates the concept
behind Rolling Sphere Method (RSM). Note that the 45 mtr
sphere sits atop the air rods, thereby providing an air
gap between the sphere and the structure.

In general, air terminals need to be installed in such
a manner so that the rolling sphere only touches their
upper interception surfaces, and when/ if the sphere
touches or breaches the outer fabric of the structure,
then additional air terminals should be installed at
those points. The values of the rolling sphere radius
are based on four protection levels:
|
Protection Level 1
|
20 Mtr Rolling Sphere
|
|
Protection Level 2
|
30 Mtr Rolling Sphere
|
|
Protection Level 3
|
45 Mtr Rolling Sphere
|
|
Protection Level 4
|
60 Mtr Rolling Sphere
|
AS1768-2007 provides the relevant radius of the rolling
sphere for each protection level, together with the corresponding
minimum lightning current (Imin) that will be intercepted.
Rolling Sphere Radius for Each Protection Level
|
Protection Level
|
Sphere Radius
|
Interception Current I min-kA
|
|
I
|
20
|
2.9
|
|
II
|
30
|
5.4
|
|
III
|
45
|
10.1
|
|
IV
|
60
|
15.7
|
For normal applications Protection Level 3 is recommended
using the 45 Mtr rolling sphere. Where munitions, fireworks
or explosives are concerned Protection Level 1 is required
using a 20 mtr rolling sphere.
Conventional Design using 45Mtr RSM

Conventional Lightning Protection Systems should be designed
and installed during a structures construction as this type
of Lightning Protection system can be difficult to retrofit
to existing buildings, and would require down conductors
to be installed vertically on the external walls every 20
mtrs. These conductors also require to be clipped every
meter or so, hence the LP system be visually unsightly and
can detract from the aesthetics of the building markedly.
During construction, structural rebar within the concrete
may be used to carry lightning current to ground where there
is a continuity of the rebar from roof to ground. Where
this continuity is not assured, the use of dedicated down
conductors is recommended.
These systems are very labor and component intensive, where
the install costs can be considerable as an overall percentage
of the systems cost.
Alternatively there is another Lightning Protection system
which is commonly used, although is outside of the scope
of the AS1768 Lightning Protection standard, the Non Conventional
“System 3000” Lightning Protection System.
Non-Conventional Systems 3000 LPS
The System 3000 is not covered in and is outside the scope
of the current AS/NZS 1768-2007 Lightning Protection standard,
but are proven to be effective and are simple and easy to
retrofit to existing buildings. The system generally require
very few down conductors, (the down conductor is a special
design coaxial cable) which are relatively flexible and
can be route current away from any sensitive areas. The
condustor can be taken down areas of the structure which
do not distract from the aesthetics. A single LPS would
require a single coaxial down-conductor.
As installation would generally take a day or so, compared
to a conventional type system, significant cost savings
can be realized by the use of System 3000

|