CRITEC PEC100 |
CRITEC® PEC – Potential
Equalization Clamp
In communications and computer installations it is not uncommon to
install separate grounds for lightning, mains power, computer (quiet
ground), and communications (for security, and tempest requirements).
Although this may be highly desirable under normal operating
conditions, when lightning or other transient voltages occur,
differences in ground potentials between the ground electrodes are
inevitable and equipment damage is the result.
The CRITEC PEC100 Potential Equalization Clamp (PEC) is an
isolation spark gap that prevents these ground potential differences
by operating under transient conditions to effectively clamp the
grounds together. Normally the PEC presents an effective open circuit.
Once the ground potential difference exceeds the breakdown voltage of
the PEC, the circuit immediately closes and the ground potentials are
equalized. The PEC is fully resettable, and has a life of over ten
thousand operations.
Note that the use of separated grounding systems is not permitted
by code in some regions and is generally NOT recommended. Where such
systems are used, the PEC offers a mechanism to minimize equipment
damage.
Many buried pipelines are protected from corrosion by cathodic
protection systems. To maintain the insulation integrity of the pipe
at metering and telemetry stations, insulating joints are inserted
into the pipe and those sections between insulating joints are
grounded at the station. With long lengths of pipelines, induced
voltages in the pipe caused by local lightning or power line faults
activity can be in the order of tens of kilovolts. The result is that
insulated joints failure is almost inevitable, with flange type
insulated joints particularly susceptible.
To protect against insulated joint break-down, the PEC can be
connected directly across the joint. In its inactive state the PEC
presents an effective open circuit across the joint. Should the
insulated joint voltage start to rise due to transients, the PEC will
conduct and safely pass the transient current to ground, limiting the
voltage stress across the joint. After conduction the PEC will
automatically reset to its inactive state.
Features:
•
100 kA (@8/20us) high peak current capability
• Fully sealed enclosure
• Explosion proof
• Can be direct buried
• Self resetting
• 5 year limited warranty
Applications:
• Equipotential bonding of systems with separate ground systems
• Protection of oil and gas pipe line insulated joints
More Information
Ordering information
|
|
Part No. |
Part No. for Europe |
Description |
|
PEC100 |
702900 |
Potential Equalization Clamp, 100kA, 350V |
| |
|
|
|