Description
Download Product Brochure herehttps://www.erico.com/part.asp?part=TDS11002SR560
FEATURES
- TD Technology with thermal disconnect protection
- Compact design fits into DIN distribution panel boards and motor control centers
- Indication flags and voltage-free contacts provide remote status monitoring
- Separate plug and base design facilitates replacement of a failed surge module
- 100kA 8/20μs maximum surge rating provides protection suitable for sub-distribution panels and a long operational life
SPECIFICATIONS
Part Number | TDS11002SR560 |
Article Number | 702413 |
Nominal System Voltage (Un) | 480 – 560 VAC |
Max Continuous Operating Voltage (Uc) | 610 VAC |
Stand-off Voltage | 700 VAC |
Voltage Protection Rating (VPR) | 1,800 V @ 3 kA 2,400 V @ 20 kA |
Nominal Discharge Current (In) | 40 kA 8/20 μs |
Max Discharge Current (Imax) | 100 kA 8/20 μs |
Impulse Current (Iimp) | 12.5 kA 10/350 μs |
Back-Up Overcurrent Protection | 125 A |
Response Time | 5 ns Max |
Short Circuit Current Rating (SCCR) | 200 kA |
Frequency | 0 – 100 Hz |
Protection Modes | L-N L-PE N-PE |
Technology | TD technology with thermal disconnect |
Connection, Solid | 35 mm² Max |
Connection, Stranded | 25 mm² Max |
Mounting | 35 mm top hat DIN rail |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 NEMA®-1 |
Remote Contacts | Yes |
Status Indication | Mechanical flag |
Temperature | -40 to 80 °C |
Module Width | 2 M |
Depth (D) | 68 mm |
Height (H) | 90 mm |
Width (W) | 35 mm |
Unit Weight | 0.24 kg |
Certification Details | UL® 1449 Edition 4 Type 4CA, 20 kA Mode |
Complies With | ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs IEC® 61643-1 Class I, Class II |
Replacement Module | TDS150M560 |
Certifications | CE cURus |
Standard Packaging Quantity | 1 pc |
UPC | 78285658538 |
EAN-13 | 8711893046267 |
Reviews
There are no reviews yet.