Description
FEATURES
- Measures earth resistance without need to disconnect from the electrical system or need for auxiliary ground electrodes or reels
- Ground Resistance is auto-ranging from 1 to 199Ω
- Current Measurement is auto-ranging from 1mA to 40A
- Ground voltage indication – warns of unsafe conditions
- Clamping diameter of 1.4″ (35 mm) with large jaw design
- Stores up to 300 measurements
- Includes a hard carrying case, calibration loop, four 1.5V AA batteries and a user manual
SPECIFICATIONS
Part Number | EST401 |
Article Number | 702390 |
Ground Resistance Measurement Range | 0.01 – 1,500.00 Ω |
Ground Resistance Resolution | 0.001 – 50.000 Ω |
Ground Resistance Accuracy | Approx. 1.5% – 25% |
Current Measurement Range | 0.20 mA – 39.99 A |
Current Measurement Resolution | 1 µA – 10 mA |
Current Measurement Accuracy | +/- 2% |
Current Measurement Frequency | 47 – 800 Hz |
Operating Frequency | 2,083 Hz |
Loop Impedance Measurement | 10 to 100μH; 100 to 500μH |
Certifications | CE |
Standard Packaging Quantity | 1 pc |
UPC | 78285660978 |
EAN-13 | 8711893045161 |